KYN-24 series of indoor withdrawout metal-clad switch cabinet
The shell of the Switchgear applies the aluminum-zinc alloy coated sheet plate brought in abroad, processed by CNC machine tool, applies multiple folding technology. The whole cabinet has the advantage of high accuracy, strong anti-corrosion and anti-oxidation ability. And for the multiple folding technology, the cabinet is much lighter than the other similar cabinet, and stronger mechanical strength. The cabinet applies the assembly structure, connected by pulling rivet and high-strength bolt. The framework of the withdrawable handcart applies thin steel plate, processed by CNC machining tool. The handcart is classified as vacuum circuit breaker handcart, voltage transformer handcart, lighting arrester handcart, isolating handcart, measuring handcart, transformer used handcart and fuse handcart. The same specification handcarts can be interchanged. The main electric components of the Switchgear has independent compartment, that is: circuit breaker handcart chamber, bus chamber, cable room, relay instrument room and so on. The protection level of all cubicles is over IP2X. The other three compartments have their own pressure release pathways except the relay instrument room. The mid-set structure greatly increase the cable room space, and thus multiple cable can be paralleled connected
Technical parameters
Serial No. | Item | Unit | Technical parameters | ||||
1 | Rated voltage | KV | 24 | ||||
2 | Rated frequency | HZ | 50/60 | ||||
3 | Rated insulation level | 1 min withstand voltage (effective value) | KV | Phase to phase & phase to earth | 60 | Isolation fracture | 79 |
Lighting impulse withstand voltage (peak value) | 125 | 145 | |||||
Auxiliary control circuit power frequency withstand voltage | V | 2000 | |||||
4 | Rated current | A | 630,1250,1600,2000,2500,3150 | ||||
5 | Specified short-circuit dropout current | KA | 20, 25, 31.5 | ||||
6 | Rated short-circuit making current (peak value) | KA | 50, 63, 80 | ||||
7 | Rated short time withstand current (4S) | KA | 20, 25, 31.5 | ||||
8 | Rated peak withstand current | KA | 50, 63, 80 | ||||
9 | Auxiliary control circuit rated voltage | V | AC or DC 110/220 | ||||
10 | Protection level | V | IP4X (the circuit breaker chamber door is open or isolation chamber is IP2X) | ||||
11 | Outline dimension | mm | 1000*1910*24001 | ||||
12 | Weight | Kg | 840-1500 |
KYN-24 series of indoor withdrawout metal-clad switch cabinet
Verified Information This information is Verified by TÜV Rheinland and validity period is 2012/09/14 --- 2013/09/14 All the information below may covers both Gold Supplier and its related companies , Their Relationship will be affirmed according to china laws and regulations , also it will be clearly display in the full report >> Production Capacity:Electrical Equipments Product Line | Power Transformer 1,000 Pieces / Month;Switchgear 8,000 Pieces / Month;Prefabricated Substation 200 Pieces / Month | Power Transformer 10,000 Pieces;Switchgear 80,000 Pieces;Prefabricated Substation 2,000 Pieces |
Eastern Europe | USD 620,000 | 0.25 |
Southeast Asia | USD 4,880,000 | 1.95 |
Africa | USD 12,000,000 | 4.8 |
Mid East | USD 3,000,000 | 1.2 |
Eastern Asia | USD 1,500,000 | 0.6 |
Central America | USD 1,000,000 | 0.4 |
South Asia | USD 2,000,000 | 0.8 |
Domestic Market | USD 225,000,000 | 90.0 |
CNC Machine | MADA-AC2510 | 5 | 2.0 | Acceptable |
Banding Machine | WC67Y-/400/2000 | 6 | 3.0 | Acceptable |
Cutting Machine | XP6255R | 12 | 3.0 | Acceptable |
Forging Machine | 123-16B | 20 | 3.0 | Acceptable |
Foil Winding Machine | RX-110 | 2 | 2.0 | Acceptable |
Vacuum Dry Machine | BP-09 | 4 | 2.0 | Acceptable |
Vacuum Injection Molding Machine | ZS-666r | 2 | 2.0 | Acceptable |
High-voltage Laboratory | No information | 5 | 5.0 | Acceptable |
CCC | CQC | CQC06021018394 | High-voltage Alternating-circuit Circuit-breakers / ZN63A-12/1250-31.5:Ur=12kv,Lr=1250A;50Hz;Lk/IP=31.5KA/80KA | 2010/06/18 --- 2049/12/31 | |
CCC | CQC | CQC06021018393 | High-voltage/Low-voltage Prefabricated Substations / IP230D,IP33D,Icw/Lpk6.3KA/16KA | 2010/06/18 --- 2049/12/31 | |
CCC | CQC | CQC06021018396 | A.C Metal-enclosed Switchgear for Rated Voltages of 3-35KV/KYN-40.5/1600-31.5;Ur=40.5kv;Lr=1600A;50Hz;IP4x;Lk/IP=31.5A/80KA | 2010/06/18 --- 2049/12/31 | |
CCC | CQC | CQC06021018398 | A.C Metal-enclosed Switchgear for Rated Voltages of 3-35KV/HXGN-12/630-20;Ur=12kv;Lr=630A;50Hz;IP3x;LK/LP=20KA/50KA,HXGN-12/125-31.5;Ur=12kv;Lr=125A;50Hz,IP3x;Ltransfen/LSC=1.7KA/31.5KA | 2010/06/18 --- 2049/12/31 |
Test report | CQC | PZ30/XL-21 | 2012/06/04 |